Products
-
360kw Electric Steam Generator
Common faults and solutions of electric heating steam generator:
1. The generator cannot generate steam. Cause: The switch fuse is broken; the heat pipe is burned; the contactor does not work; the control board is faulty. Solution: Replace the fuse of the corresponding current; Replace the heat pipe; Replace the contactor; Repair or replace the control board. According to our maintenance experience, the most common faulty components on the control board are two triodes and two relays, and their sockets are in poor contact. In addition, various switches on the operation panel are also prone to failure.2. The water pump does not supply water. Reasons: the fuse is broken; the water pump motor is burned; the contactor does not work; the control board is faulty; some parts of the water pump are damaged. Solution: replace the fuse; repair or replace the motor; replace the contactor; replace damaged parts.
3. The water level control is abnormal. Reasons: electrode fouling; control board failure; intermediate relay failure. Solution: remove the electrode dirt; repair or replace the control board components; replace the intermediate relay.
4. The pressure deviates from the given pressure range. Reason: deviation of pressure relay; failure of pressure relay. Solution: readjust the given pressure of the pressure switch; replace the pressure switch.
-
54kw Electric Steam Generator
How to use, Maintenance and Repair of Electric Heating Steam Generator
In order to ensure the normal and safe operation of the generator and prolong the service life of the equipment, the following rules of use should be observed:1. The medium water should be clean, non-corrosive and impurity-free.
Generally, soft water after water treatment or water filtered by a filter tank is used.2. In order to ensure that the safety valve is in good condition, the safety valve should be artificially exhausted 3 to 5 times before the end of each shift; if the safety valve is found to be lagging or stuck, the safety valve must be repaired or replaced before it can be put into operation again.
3. The electrodes of the water level controller should be cleaned regularly to prevent the electric control failure caused by electrode fouling. Use a #00 abrasive cloth to remove any buildup from the electrodes. This work must be done with no steam pressure on the equipment and with the power cut off.
4. In order to ensure that there is no or little scaling in the cylinder, the cylinder must be cleaned once every shift.
5. In order to ensure the normal operation of the generator, it must be cleaned once every 300 hours of operation, including electrodes, heating elements, inner walls of cylinders, and various connectors.
6. In order to ensure the safe operation of the generator; the generator must be checked regularly. Regularly inspected items include water level controllers, circuits, the tightness of all valves and connecting pipes, the use and maintenance of various instruments, and their reliability. and precision. Pressure gauges, pressure relays and safety valves must be sent to the superior measurement department for calibration and sealing at least once a year before they can be used.
7. The generator should be inspected once a year, and the safety inspection should be reported to the local labor department and carried out under its supervision.
-
48kw Electric Steam Generator
The principle of electric heating steam generator
The working principle of the electric heating steam generator is: when the water supply system supplies water to the cylinder, when the water level rises to the working water level line, the electric heating element is powered on through the water level controller, and the electric heating element works. When the water level in the cylinder rises to a high water level, the water level controller controls the water supply system to stop supplying water to the cylinder. When the steam in the cylinder reaches the working pressure, the required pressure steam is obtained. When the steam pressure rises to the set value of the pressure relay, the pressure relay will act; cut off the power supply of the heating element, and the heating element will stop working. When the steam in the cylinder drops to the lower value set by the pressure relay, the pressure relay will act and the heating element will work again. In this way, an ideal, certain range of steam is obtained. When the water level in the cylinder drops to a low level due to evaporation, the machine can automatically cut off the power supply of the heating element to protect the heating element from being burned out. While cutting off the heating element power supply, the electric bell alarm sounds and the system stops working. -
90kg Industrial steam Generator
How to judge whether the steam boiler is energy-saving
For the majority of users and friends, it is very important to purchase a boiler that can save energy and reduce emissions when purchasing a boiler, which is related to the cost and cost performance of the subsequent use of the boiler. So how do you see whether the boiler is an energy-saving type when purchasing a boiler? Nobeth has summarized the following aspects to help you make better boiler selection.
1. When designing the boiler, the reasonable selection of equipment should be carried out first. In order to ensure that the safety and energy saving of industrial boilers meet the requirements of users, it is necessary to choose the appropriate boiler according to the local conditions, and design the boiler type according to the scientific and reasonable selection principle.
2. When selecting the type of boiler, the fuel of the boiler should also be correctly selected. The type of fuel should be reasonably selected according to the type, industry, and installation area of the boiler. Reasonable coal blending, so that the moisture, ash, volatile matter, particle size, etc. of the coal meet the requirements of imported boiler combustion equipment. At the same time, encourage the use of new energy sources such as straw briquettes as alternative fuels or blended fuels.
3. When selecting fans and water pumps, it is necessary to choose new high-efficiency and energy-saving products, and not to choose outdated products; match the water pumps, fans and motors according to the operating conditions of the boiler to avoid the phenomenon of “big horses and small carts”. Auxiliary machines with low efficiency and high energy consumption should be modified or replaced with high-efficiency and energy-saving products.
4. Boilers generally have the highest efficiency when the rated load is 80% to 90%. As the load decreases, the efficiency will also decrease. Generally, it is sufficient to select a boiler whose capacity is 10% larger than the actual steam consumption. If the selected parameters are not correct, according to the series standards, a boiler with a higher parameter can be selected. The selection of boiler auxiliary equipment should also refer to the above principles to avoid “big horses and small carts”.
5. To reasonably determine the number of boilers, in principle, the normal inspection and shutdown of the boilers should be considered. -
2Ton gas steam boiler
What are the factors affecting the quality of steam generators
The gas steam generator that uses natural gas as the medium to heat the gas can complete high temperature and high pressure in a short time, the pressure is stable, no black smoke is emitted, and the operating cost is low. It has high efficiency, energy saving, intelligent control, convenient operation, safety and reliability, environmental protection, and Simple, easy maintenance and other advantages.
Gas generators are widely used in auxiliary food baking equipment, ironing equipment, special boilers, industrial boilers, clothing processing equipment, food and beverage processing equipment, etc., hotels, dormitories, school hot water supply, bridge and railway concrete maintenance, sauna, heat exchange Equipment, etc., the equipment adopts a vertical structure design, which is convenient to move, occupies a small area, and effectively saves space. In addition, the application of natural gas power has fully completed the policy of energy conservation and environmental protection, which meets the basic requirements of my country’s current industrial production and is also trustworthy. products, and get customer support.
Four elements that affect the steam quality of gas steam generators:
1. Pot water concentration: There are many air bubbles in the boiling water in the gas steam generator. With the increase of the pot water concentration, the thickness of the air bubbles becomes thicker and the effective space of the steam drum decreases. The flowing steam is easily brought out, which reduces the quality of the steam, and in severe cases, it will cause oily smoke and water, and a large amount of water will be brought out.
2. Gas steam generator load: If the gas steam generator load is increased, the rising speed of the steam in the steam drum will be accelerated, and there will be enough energy to bring highly dispersed water droplets out of the water surface, which will deteriorate the quality of the steam and even cause serious consequences. The co-evolution of water.
3. Gas steam generator water level: If the water level is too high, the steam space of the steam drum will be shortened, the amount of steam passing through the corresponding unit volume will increase, the steam flow rate will increase, and the free separation space of water droplets will be shortened, resulting in water droplets and steam together Going forward, the steam quality deteriorates.
4. Steam boiler pressure: When the pressure of the gas steam generator suddenly drops, add the same amount of steam and the amount of steam per unit volume, so that small water droplets will be easily taken out, which will affect the quality of the steam. -
1T oil steam boiler
Nobles steam generator features:
1. The internal volume of the generator is less than 30L
2. The shell is made of stainless steel, which has high strength, corrosion resistance and long service life.
3. Steam can be produced in 5 minutes, continuous high-pressure steam production, the maximum pressure is 0.7Mpa.
4. The device is easy to install, and can be used when connected to water, electricity and steam.
5. The equipment is small in size and easy to move.
6. A waste heat recovery module is added inside the equipment, which can make the thermal efficiency of the overall equipment reach more than 95%. -
2T Fuel Oil Gas Steam Boiler
1. The machines are inspected and quality certified by the National quality supervision department before delivery.
2. Produce steam fast, stable pressure, no black smoke, high fuel efficiency, low operating cost.
3. Imported burner, automatic ignition, automatic fault combustion alarm and protection.
4. Responsive, easy to maintain.
5. Water level control system, heating control system, pressure control system installed. -
1T gas oil steam generator
Large-scale industrial manufacturing
The main use of clean steam in pharmaceutical manufacturing is for the sterilization of products or, more usually, equipment. Steam sterilization is encountered in the following processes
Manufacture of injectable or parenteral solutions, which are alwayssterile Biopharmaceutical manufacturing, where a sterile environment must be created to grow the biological production organism(bacterium yeast or animal cell) Manufacture of sterile solutions, such as ophthalmic products. Typically in these processes, clean steam is injected into equreloose piping to create a sterile environment, or into autoclaves where loose equipment, components(such as vials and ampoules )or products are sterilized . Clean steam may be used for some other functions where conventional utility steam might cause contamination, such as Humidification in some clean rooms. Injection into high purity water for heating prior to Clean-in-Place (CIP)operations .
-
0.05T oil gas steam boiler
Features:
1. The machines are inspected and quality certified by the National quality supervision department before delivery.
2. Produce steam fast, stable pressure, no black smoke, high fuel efficiency, low operating cost.
3. Imported burner, automatic ignition, automatic fault combustion alarm and protection.
4. Responsive, easy to maintain.
5. Water level control system, heating control system, pressure control system installed. -
12kw Electric Steam Generator
Applications:
Our boilers offer a diverse range of energy sources including waste heat and reduced running costs.
With clients ranging from hotels, restaurants, event providers, hospitals and prisons, a vast amount of linen is outsourced to laundries.
Steam boilers and generators for the steam, garment and dry cleaning industries.
Boilers are used to supply steam for commercial dry cleaning equipment, utility presses, form finishers, garment steamers, pressing irons, etc. Our boilers can be found in dry cleaning establishments, sample rooms, garment factories, and any facility that presses garments. We often work directly with equipment manufacturers to provide an OEM package.
Electric boilers make an ideal steam generator for garment steamers. They are small and require no venting. High pressure, dry steam is available directly to the garment steam board or pressing iron a quick, efficient operation. The saturated steam can be controlled as to pressure -
4KW electric steam boiler
Application:
Used in a range of applications from cleaning and sterilisation to steam sealing, our boilers are trusted by some biggest pharmaceutical manufacturers.
Steam is a vital part to the Pharma industry’s manufacturing. It offers huge savings potential for any pharmaceutical employing steam generation by reducing fuel costs.
Our solutions have been used globally within the laboratories and manufacturing facilities of numerous Pharmaceuticals. Steam offers an ideal solution to an industry that sustains utmost standards of manufacturing capabilities because of its flexible, reliable and sterile qualities.
-
6KW electric steam boiler
Features:
The product adopts high-quality universal casters and moves freely. The fastest heating in same power among all products. Use high quality high pressure vortex pump, low noise, not easy to damage; Simple overall structure, cost-effective, food production preferred.